Description
Conductor
- Material : Oxygen free copper (99.97% purity)
- Diameter : 0.57 mm ± 0.01 mm (0.0224" ± 0.0004")
- Wire Gauge : 23 AWG
Insulation
- Material : HDPE
- Min. Average Thickness : 0.21 mm (0.0083")
- Diameter : 1.12 mm ± 0.1 mm (0.04" ± 0.0004")
- Color : 8 cores, Blue, white/blue; Orange, white/orange; Green, white/green; Brown, white/brown
Rip Cord
- Material : Polyester
- Specification : 500D
Drain Wire
- Material : Tinned copper
- Specification : 0.50 mm ± 0.01 mm (0.0004" × 0.02")
Separator
- Material : PE
- Specification : Translucent 5.2 mm × 0.6 mm (0.21" × 0.02")
Wrapping Tape
- Material : Polyester tape (transparent)
- Thickness : 0.025 mm × 25 mm (0.001" × 0.98")
Outer Shield
- Material : Aluminum foil
- Specification : 0.06 mm × 25 mm (0.002" × 0.98")
Sheath
- Material : PVC
- Min. Average Thickness : 0.55 mm (0.0216")
- Diameter : 7.3 mm ± 0.4 mm (0.2874" ± 0.0157")
- Color : Gray
Electrical
- Max. DC Resistance of a Single Conductor : 7.35 Ω / 100 m (328.08 ft)
- Min. Insulation Resistance : 5000 MΩ·km
- Max. DC Resistance Unbalance : 2% (pair intra), 4% (pairs inter)
- Dielectric Strength : No breakdown with 1kV DC for 1 min
Transmission
- Characteristic Impedance : 100 Ω ± 15 Ω
- Near-end Crosstalk : ≥33.10 dB / 100 m @ 250 MHz
- Max. Attenuation : 32.8 dB / 100 m @ 250 MHz
- Return Loss : ≥17.3 dB / 100 m @ 250 MHz
Mechanical
- Tensile Strength : Sheath ≥13.5 MPa, Insulation ≥16 MPa
- Elongation at Break : Sheath ≥150%, Insulation ≥300%
- Installation Bending Radius : >8 times of outer cable diameter
- Conductor Elongation at Break : ≥10%
Environmental
- Shrinkage of Insulation : ≤5%
- Color Migration Resistance of Insulation : No migration
- Sheath Tensile Strength and Elongation at Break after Aging : ≥12.5 MPa, ≥125%
- Low Temperature Bending Test : No cracking after the test
- Heat Shock Test : No cracking after the test
- Operating Temperature : –20 °C to +60 °C (–4 °F to +140 °F)
- Installation Temperature : 0 °C to +50 °C (32 °F to 122 °F)
- Storage Temperature and Humidity : –10 °C to +40 °C (14 °F to 104 °F), <60% (RH)
Security
- Vertical Flame Test : Complies with IEC 60332-1-2
Packaging
- Cable Length : 305.0 m ± 2 m (1000.66 ft ± 6.56 ft)
- Packaging Method : 305 m (1000 ft) a carton, one carton with 2 inner cartons
- Packaging Dimensions : 414 mm × 321 mm × 425 mm (16.3" × 12.64" × 16.73") (L × W × H)
- Net Weight : 19.3 kg ± 0.6 kg (42.55 lb ± 1.32 lb)
- Gross Weight : 20.3 kg ± 0.5 kg (44.75 lb ± 1.32 lb)
Compliance
- Executive Standards : ISO/IEC 11801, IEC 61156
- Certifications : CPR Eca
- Flame-retardant Standard : EN50575