Description
Communication (Jeweller)
-
Technology: Proprietary wireless communication to transmit commands, alarms, and events
-
Key features: Two‑way communication; advanced sabotage protection; block encryption with dynamic key; instant notifications; remote control and configuration in Ajax apps
-
Frequency bands (depends on sales region):
-
866.0–866.5 MHz
-
868.0–868.6 MHz
-
868.7–869.2 MHz
-
905.0–926.5 MHz
-
915.85–926.5 MHz
-
921.0–922.0 MHz
-
-
Maximum ERP: up to 20 mW
Automatic power control reduces power consumption and radio interference -
Radio modulation: GFSK
-
Radio communication range: up to 1,700 m (open space) between the device and a CIE or range extender
-
Encrypted communication: Block encryption with dynamic key for stored and transmitted data
-
Frequency hopping: To prevent radio interference and jamming
Inputs
-
Number of input lines for third‑party devices: 2
-
Input terminals:
-
Input 1, Input 2 — inputs for connecting third‑party wired devices
-
Shield — common input for connecting shields of cables that connect third‑party wired devices
-
-
Type of connection: NO, NC, EOL, 2EOL, 3EOL
-
EOL resistance: 0.47 kΩ, 1.2 kΩ, 2.7 kΩ, 6.2 kΩ
Four resistors for each input are included in the complete set -
Length of wired connection to third‑party devices: up to 100 m (with 2×1.5 mm² / 16 AWG fire‑resistant cable)
-
Cable cross‑section: 0.4–2.5 mm² (21–13 AWG)
Outputs
-
Number of output lines for third‑party devices: 2
-
Output terminals: Output 1, Output 2 — relay outputs for connecting third‑party wired devices
-
AC operating range: 10—250 V~; 5 mA to 10 A (resistive load)
-
DC operating range: 10—30 V⎓; 5 mA to 5 A (resistive load)
-
Cable cross‑section: 0.4–2.5 mm² (21–13 AWG)
Key Features & Behaviour
-
Event types: Configurable in Ajax apps (PRO or user with admin rights). Selected type determines notification texts and CMS event codes for connected wired devices
-
Fail‑safe mode: If the module is offline, discharged, or has hardware problems, it automatically activates the connected devices
-
Installation: Indoor use only
Sabotage & Integrity Protection
-
Tamper alarm: Notifies attempts to detach the module from the surface or open the front lid
-
Protection against spoofing: Device authentication
-
Connection loss detection: After 36 s (depends on Jeweller settings)
-
Input monitoring: Detection of wired connection loss, short circuits, and malfunctions when EOL/2EOL/3EOL connection is used (depends on connection type)
Power
-
Battery: 2 × CR123A (pre‑installed)
-
Calculated battery life: up to 5 years
Casing
-
Dimensions: 116 × 180 × 62 mm
-
Weight: 547 g
-
Operating temperature range: 0 °C to +50 °C
-
Operating humidity: up to 80%
-
Protection class: IP21C
-
Flammability rating: UL 94 V‑0
-
Colors: Black, White
Complete Set
-
EN54 I/O Module (2×2) Jeweller
-
2 × CR123A battery (pre‑installed)
-
Installation kit
-
2 × set of 4 EOL resistors
-
Quick start guide